AMS 4710 - pressure transmitter with voltage output 0-10 V by AMSYS

AMS 4710 – pressure transmitter with voltage output

Schaltplan AMS 4711-Drucktransmitter mit Spannungsausgang 0-5V by AMSYS

Electrical connection of AMS 4711 also applies to the AMS 4710

The AMS 4710 sensor is part of a series of miniaturized analog pressure transmitters* ready-to-use in HVAC and air filter control. AMS 4710 is designed for fast screw assembly in a harsh industrial environment and fits for absolute, differential, gage and bidirectional differential pressure measurement.

One process of AMS 4710 production is the calibration as well as the compensation of temperature dependent drift of offset and span. No additional adjustment on the part of the customer is necessary. The sensor provides a 0…10 V output signal at 12 – 36 V voltage supply.

An integrated CMOS-DSP and EEPROM allow high accuracy in measurement capability. AMS 4710 comes in a robust and compact plastic package (IP67) and is unilaterally mediaresistent due to underside pressurization*.

Pressure types and ranges for the AMS 4710

AMS 4710 (ultra low pressure) pressure ranges: differential or bidirectional differential: 0-5; 0-10 mbar or ±5 and ±10 mbar

AMS 4710 (low pressure) pressure ranges: differential or bidirectional differential: 0-20; 0-50; 0-100 mbar or ±20; ±50 and ±100 mbar

AMS 4710 pressure ranges: gage, differential or bidirectional differential: 0-200; 0-350; 0-1000 and 0-2000 mbar or ±200; ±350 and ±1000 mbar

AMS 4710 pressure ranges: absolute 1000 and 2000 mbar

AMS 4710 pressure range: barometric (absolute) 700-1200 mbar

Note: The AMS 4710 can also be calibrated to meet customer specifications. Further variants of the transmitter family are the AMS 4711 with a 5 V output, the AMS 4712 with a fault-resistant 4-20 mA output and the AMS 3010 in a rugged metal housing for high system pressure*.

Accessory

Connection cable for pressure sensors AMS 471X: Related M5 cable

Features

  • High accuracy in measurement
  • Relative, absolute and differential pressure ranges 5 mbar to 2 bar
  • Low total error between -25…+85ºC
  • 0…10 V-Output signal
  • Wide range of supply voltage
  • High resolution
  • Maintenance-free
  • Product “Made in Germany”
  • Simplest installation, quick start of operation
  • RoHS and REACH compliant

Applications

  • Barometric measurement
  • Monitoring of industrial filters
  • HEPA filter control
  • Pneumatic control
  • Monitoring of vacuum, Heating, Ventilation and Air Conditioning (HVAC)
  • Level sensing
  • Over- and under pressure measurement

For information on prices and delivery times or if you have any technical questions, please contact info@amsys-sensor.com.